Inverter Commercial Heat Pump
Commercial inverter heating heat pumps can be used in a wide variety of settings including hotels, hospitals, corporate events, restaurants, commercial shopping malls, and manufacturing plants.
Highlights:
High Performance Commercial Monoblock inverter heat pump.
Power Range 14-50kW
– Max 16 Units is cascade Control
– Smart Defrosting
– 4G DTU or WiFi remote Monitoring and Control
– Energy Stage Control
– Leakage Monitor
– Full Inverter Technology
– Minimum outdoor temperature up to -25°C for R290 models
– GWP3
Wide Operation Range
Running safely and reliably all year round, ICEBERG perfectly combines eco-friendly R290 natural refrigerant and inverter heating technology to ensure optimal performance from -25℃ to 43℃. It’s worth mentioning that the unit can operate efficiently at -25°C, maintaining high COP, reliable stability, and strong heating capacity for 60℃ hot water. More significantly, the maximum outlet water temp can be up to 75℃ without electric heating to guarantee protection against legionella. It can connect to solar water heating systems, various gas boiler water heating systems and electric water heating systems.
Full DC Inverter Technology
Color Display
DC Inverter Motor
DCInverter Compressor
SPECIFICATIONS:
Rated Heating A20/W55°C | Heating Capacity | kW | 40.00 |
Heating Power Input | kW | 8.50 | |
COP | / | 4.70 | |
Rated Heating One A7/W45°C | Heating Capacity | kW | 41.5(16.0~50.0) |
Heating Power Input | kW | 12.2(4.5~17.5) | |
COP | / | 3.40(2.86~3.65) | |
Rated Heating Two A-12/W41°C | Heating Capacity | kW | 30.0(11.3~33.2) |
Heating Power Input | kW | 13.0(4.7~15.8) | |
COP | / | 2.31(2.10~2.75) | |
Rated Heating Three A-20/W41°C | Heating Capacity | kW | 24.2(13.2~26.9) |
Heating Power Input | kW | 12.5(6.6~14.6) | |
COP | / | 1.94(1.84~2.12) | |
Heating IPLV (H) | / | 3.25 | |
Power Supply | / | 380 -415V/3N~/50~60Hz | |
Max. Power Input | kW | 18.50 | |
Max. Running Current | A | 29.50 | |
Operating Temperature Range | °C | -38~55 | |
Refrigerant | R410a, R32 on request | ||
Water Flow Volume | hot water | m³/h | 6.88 |
heating (-12/-14°C) | m³/h | 5.70 | |
Water Pressure Drop | hot water | kPa | 75.00 |
heating (-12/-14°C) | kPa | 50.00 | |
Water Connection | / | DN40 | |
Noise | dB(A) | 61(56~65) | |
Net Weight | Kg | 490.00 | |
Gross Weight | Kg | 560.00 | |
Dimentions | mm | 1195/980/1900 |