Inverter Commercial Heat Pump
Commercial inverter heating heat pumps can be used in a wide variety of settings including hotels, hospitals, corporate events, restaurants, commercial shopping malls, and manufacturing plants.

Highlights:
Large · 2 fans · 2 circuits
Energy class 35 / 55 °C A+++ / A++
Operating range −25 ~ +43 °C
Max outlet temp. +70 °C
R290 Safety System
NDIR leak detector + ATEX certified exhaust fan + R290 degasser + refrigerant relief valve — fully integrated, no external safety kit required.
Slide Defrost Technology
Advanced slide defrost with EEV liquid hammer protection. Refrigerant pressure & temperature monitored by main PCB at all times for stable performance.
Plate Heat Exchanger · SS316
Brazed stainless steel SS316 plate HEX — handles full water range up to +70 °C. Anti-freeze valve with drain system + manual drain for winter maintenance.
Full DC Inverter Compressor
4-layer insulated, wide operational range with stepless modulation — exceptional efficiency vs fixed-speed tandem units, stable output from minimal to peak load.
Hybrid Boiler Function
Works alongside existing gas boilers in boiler / hybrid / renewable modes. Ideal for commercial retrofits. SG Ready.
Cascade up to 32 Units
One 10″ central display manages up to 32 units via Modbus RS485 — balance & shift operation, SG Ready, phased investment.
Inverter Pump + Energy Meter
Built-in inverter water pump for efficient hydronic energy transfer. Integrated electricity meter measures consumption for cost tracking and intelligent control.
Weather-compensated Control
Adjusts flow temperature to the outdoor weather curve — maximum comfort at the lowest efficient water temperature.
SPECIFICATIONS:
| HEATING — A 7 / W 35 ( °C) EN 14511 | |
| Nominal capacity, kW | 50 |
| Capacity range, kW | 22.09 – 80.00 |
| COP range, W/W | 3.64 – 4.60 |
| HEATING — A-7/ W55 ( °C) EN 14511 | |
| Capacity range, kW | 12.03 – 43.00 |
| COP range, W/W | 1.89 – 2.79 |
| SEASONAL PERFORMANCE ( SCOP) EN 14825 | |
| SCOP at 35 °C | 4.58 |
| SCOP at 55 °C | 3.67 |
| SCOP at 65 °C | 3.16 |
| COOLING — A 35/ W 7 ( °C) | |
| Capacity range, kW | 17.18 – 62.00 |
| EER range, W/W | 2.47 – 3.65 |
| COMPRESSOR, ELECTRICAL G HYDRAULIC | |
| Compressor type / brand | Hitachi Scroll |
| Fan type / qty | DC Fan ×2 |
| Max power / current, kW / A | 36 / 45 |
| Refrigerant / charge | R290 / 3800 g × 2 |
| Power supply, V / Ph / Hz | 380–415 / 3N~ / 50 |
| Water connection / flow, inch / m³/h | G 2″ / 8.6 |
| DIMENSIONS, WEIGHT G ACOUSTICS EN 12102 | |
| Unit dimension L×W×H, mm | 1965×1060×1900 |
| Net weight, kg | 635 |
| Sound power / pressure 1 m, dB(A) | 56 / 73 |

CP701 7″ Wired Display
Single-unit wired controller
with new UI. Modes: Heating
· Cooling · DHW, plus
Composite mode —
simultaneous heating + DHW
for projects needing space
heating and hot water
together.
Included in standard
supply.

CP502 10″ Centralized
Controller
Central cascade controller
with LAN / Ethernet for
remote management over the
internet. Manages up to 32
units — multi-mode, balance
& shift operation, curve
recording and remote
firmware upgrade.
Optional.