NOTT – Fresh Air Heat Pump

Fresh Air Heat Pump

AC-HTPF35AV-HTPF60AV-HTPF90
AIRFLOW & PRESSURE
Rated airflow, m³/h350620950
External static pressure, Pa100100100
VENTILATION MODE — ENERGY RECOVERY
Recovery typeEnthalpy (HPERV)
Temperature efficiency (heating), %777877
Temperature efficiency (cooling), %727273
Enthalpy efficiency (heating), %767770
Enthalpy efficiency (cooling), %706566
Input power (ventilation mode), W185451788
Input current (ventilation mode), A1.673.773.93
COOLING — INDOOR 27 °C/19.5 °C · OUTDOOR 35 °C/28 °C
Nominal cooling capacity, kW3.86.48.3
Input power (cooling), kW0.851.241.49
EER4.485.145.58
HEATING — INDOOR 21 °C/13 °C · OUTDOOR 2 °C/1 °C
Nominal heating capacity, kW4.66.38.9
Input power (heating), kW0.791.031.43
COP5.866.096.22
ELECTRICAL & ACOUSTICS
Compressor / fansDC inverter compressor · EC fans
Power supply220 V~ / 50–60 Hz, 1 Ph
Sound power level, dB(A)37 / 4240 / 44.641 / 46
RefrigerantR32
Refrigerant charge, g370500660
PHYSICAL
Unit dimension W×L×H, mm600×760×1100740×1050×990740×1090×1130
Air inlet / outlet diameter, mm195245245
Net weight, kg135165190